Wire size guide

⚠ Safety first. High-voltage, high-current battery systems can cause fire, severe burns and electrocution. Builds involving these systems should be done or inspected by a qualified professional. This page is general information only, not engineering advice; follow your parts makers' instructions and local codes.

Calculator

Minimum: —

Ampacity table (copper, 75°C insulation)

GaugeAmpacityDC resistance (Ω/1000 ft)
14 AWG20 A3.07
12 AWG25 A1.93
10 AWG35 A1.21
8 AWG50 A0.764
6 AWG65 A0.491
4 AWG85 A0.308
3 AWG100 A0.245
2 AWG115 A0.194
1 AWG130 A0.154
1/0 AWG150 A0.122
2/0 AWG175 A0.0967
3/0 AWG200 A0.0766
4/0 AWG230 A0.0608

Sources: ampacity from NFPA 70 (National Electrical Code) Table 310.16, copper, 75°C column, not more than three current-carrying conductors, 30°C ambient. Resistance from NEC Chapter 9 Table 8 (uncoated copper, 75°C). NEC tables are for building wiring; fine-strand welding/battery cable with higher-temp insulation may be rated higher by its maker — use the maker's rating. Peak (launch) currents above these values are short-duration; size for continuous current and protect every cable with a correctly rated fuse. Voltage drop target here: ≤3% round trip.